400-770-9799

鄂尔多斯1A数据中心
Ordos 1A Data Center


西北首个获得美国UPTIME TIER Ⅲ设计认证和美国LEED认证的绿色数据中心
The 1st Data Center Acquired Uptime Tier III and U.S. Green Building Council LEED Certification in Northwest China

鄂尔多斯国际绿色信息港1A数据中心坐落于内蒙古鄂尔多斯市云计算产业园区,紧邻东康快速路30分钟即可驱车到达机场、1小时飞抵北京;设计等级Uptime Tier III、新国标A级, 20145月投入运行,主要服务于内蒙古自治区政府、金融机构及大型互联网企业,重点开展异地灾备业务。

Ordos International Information Harbor Data Center 1A (referred to as “Ordos Data Center 1A”) is located in Ordos Cloud Computing Industry Park in Inner Mongolia, adjacent to Dongkang Expressway, 30 minutes’ drive from the airport, 1 hour’s flight from Beijing. Its design level is Uptime Tier III, equivalent to grade A of the new national standard. Focusing on remote disaster recovery business, 1A has mainly served Inner Mongolia government, financial institutions and large internet companies since its opening in May 2014.


机房特色
Features

  • 鄂尔多斯1A数据中心采用中轴对称设计,在机房区域两侧对称设置了4个电池间、4个配电间、4个UPS配电室和2个电信接入间,所有基础设施达到2N容灾备份的标准、并通过物理隔离提高了整体安全性。
    Ordos Data Center 1A is designed symmetrically with 4 battery rooms, 4 electrical distribution rooms, 4 UPS distribution rooms and 2 network access rooms. These infrastructures are equally arranged at both sides. For disaster recovery, the design of all infrastructures is 2N redundant. And the physical isolation of the infrastructures secures the whole data center safety further.

  • 得益于鄂尔多斯寒冷的气候条件、及充足的电力资源,鄂尔多斯1A数据中心全年拥有长达7个月的完全自然冷却时间,实际运营PUE低至1.36。
    Thanks to Ordos’ cool weather and abundant electricity power, Ordos Data Center 1A has a natural cooling period as long as 8 months, achieving the operational PUE value as low as 1.36.


  • 2014年12月获颁美国Uptime Tier III认证证书;2015年6月获颁美国绿色建筑协会LEED认证证书。
    1A was obtained Uptime Tier III Certification in December 2014 and U.S. Green Building Council LEED Silver Certification in June 2015.

  • 2015年11月建成北京至鄂尔多斯的网络直连光纤链路;2017年5月在原有电信网络基础上,进一步接入联通、移动200G国干网络,大幅提升网络性能。
    In November 2015, the fiber-optic direct link connected Ordos with Beijing was built. In May 2017, the 200G backbone network link to  China Unicom and China Mobile were built, Ordos network performance has been improved substantially.


础数据
Basic Data

模块编号
Module No.

MR1

MR2

MR3

MR4

MR5

PMDC1~10

网络机房A
Network Room A

网络机房B
Network Room B

测试机房
Testing Room

合计
Total

机柜数量(R)
Racks

205

204

205

205

120

19×10

22

22

52

1225

模块面积()
Module Area

365

360

360

360

220

577

143

138

145

2668




设参数
Co
nstruction Parameters

  • 位置 Location

内蒙古鄂尔多斯市高新区云计算产业园
Ordos Cloud Computing Industry Park,
High-tech Industry Park,
Ordos, Inner Mongolia



  • 建筑设计 Building

独栋,单层钢框架结构
Detached building, monolayer steel-frame structure

层高7.2米
Story height: 7.2m

地板承重16KN/m2
Loading capacity: 16KN/

  • 电力系统 Power Supply

双系统双路供电,来自两个不同变电站,总供电容量26400KVA
Dual systems dual paths supported by two different substations; power supply capability: 26,400KVA

UPS系统2N冗余配置,满载后备供电15分钟
UPS system with 2N redundant configuration; UPS battery backup time at rated load: 15 minutes

柴油发电机采用N+1配置,市电中断后1分钟内供电,满载后备供电36小时
Diesel generator with N+1 redundant configuration, power supply in 1 minutes after electricity cut, 36 operating hours without refueling

单机柜电力20~30A,可按需改造
Each rack power: 20~30A; Partial rack power could be expanded

  • 制冷系统 Air Conditioning

机房使用精密空调调节室内温度和湿度
Precision air-conditioners control IDC temperature and humidity

空调系统采用UPS电源供电,空调冗余N+1
N+1 redundant air-conditioning system powered by UPS

地板下送风,上回风;冷通道封闭(冷热通道严格隔离)
Down-flow air supply, up-flow air return, enclosed cold passages (cold and hot passages are isolated)

水冷,给水中断的情况下系统48小时的正常运行;蓄冷罐15分钟不间断制冷
Water cooling system operates 48 hours without water supply; cold storage tank provides 15 minutes’ cooling in case chillers fail

  • 防系统 Fire-fighting

模块机房采用IG541自动气体灭火系统;云箱采用FM200自动气体灭火系统
Modular rooms equipped with IG541 automatic gas fire-fighting system, DC containers equipped with FM200 automatic gas fire-fighting system

分区相互独立,可以实现分区灭火,此外配备手持式灭火器及空气呼吸器
Independent zone for fire-fighting separately, each zone equipped with handheld extinguishers and air-breathers

消防与空调、新风、门禁、计算机供电和市电等系统联动
Linked air-conditioning system, air system, access control system, computer power supply system and city power system etc.

  • 安保系统 Security

视频监控系统,另可根据用户需求定点增加高清摄像设备
Monitoring cameras; HD cameras could be added as needed on spot

授权门禁系统、红外探测、电子围栏
Access control system, infrared detection, electronic fences

人员权限设置,设备安全管理,多层安全防范与管理
Staff permission setting, devices safety management, multi-levels security protection and management



  • 络环境 Connectivity

中国电信、中国联通、中国移动等
Backbone network link to China Telecom, China Unicom, China Mobile etc.

多线均万兆对接,可随时根据实际需求进行扩容
Tens of gigabit multiline access, scalable as needed

国内首条第三方正式运营的鄂尔多斯到北京光纤直连链路
The first China 3rd party running fiber-optic direct link connected Ordos with Beijing

  • 管理服务 Mantenance and Operation Services

7×24小时值守,5分钟内响应,15分钟内应急处理反馈
7×24 hours guarding, quick response in 5 minutes, emergency processing and feedback in 15 minutes

拥有完备的应急方案、完善的应急管理流程,切实保障业务连续性
Complete emergency solutions and emergency management process to guarantee business continuity



上一篇:无